The measuring instrument for ambient air conditions, for assessing Indoor Air Quality and adjusting and inspecting VAC systems. testo 435-1 is an affordable introduction to measurement engineering for ambient air conditions. The IAQ probe measures Indoor Air Quality by measuring CO2 level, air moisture and air temperature. Temperature and humidity measurement is integrated in the thermal probe. In addition, it is also possible to connect additional temperature probes. Readings from up to 3 temperature probes can be displayed in the clearly laid-out measuring instrument display; data transmission is radio-controlled, therefore wireless. Measurement data is printed on site on the Testo printer.
- IAQ probe for assessment of Indoor Air Quality
- Vane measurement and thermal probes
- Radio probe for temperature
- Testo fast printer for documentation
- Protection class IP54
|
Storage temperature
|
-30 to +70 °C
|
|
Operating temperature
|
-20 to +50 °C
|
|
Battery type
|
Alkali manganese, mignon, Type AA
|
|
Battery life
|
200 h (typical vane measurement)
|
|
Weight
|
428 g
|
|
Dimensions
|
220 x 74 x 46 mm
|
|
Material/Housing
|
ABS/TPE/Metal
|
|
Probe - Type T (Cu-CuNi)
|
|
Meas. range
|
-200 to +400 °C
|
|
Accuracy
|
±0.3 °C (-60 to +60 °C)
±(0.2 °C +0.3% of mv) (remaining range)
|
|
Resolution
|
0.1 °C
|
|
Probe - NTC
|
|
Meas. range
|
-50 to +150 °C
|
|
Accuracy
|
±0.2 °C(-25 to +74.9 °C)
±0.4 °C (-50 to -25.1 °C)
±0.4 °C (+75 to +99.9 °C)
±0.5% of mv (remaining range)
|
|
Resolution
|
0.1 °C
|
|
Probe - Type K
|
|
Meas. Range
|
-200 to +1370 °C
|
|
Accuracy
|
±0.3 °C (-60 to +60 °C)
±(0.2 °C +0.3% of mv) (remaining range)
|
|
Resolution
|
0.1 °C
|
|
Probe - CO2
|
|
Meas. Range
|
0 to +10000 ppm CO2
|
|
Resolution
|
1 ppm CO2
|
|
Probe - Absolute pressure probe
|
|
Meas. Range
|
0 to +2000 hPa
|
|
Resolution
|
0.1 hPa
|
|
Probe - humid. sensor, cap.
|
|
Meas. Range
|
0 to +100 %RH
|
|
Resolution
|
0.1 %RH
|
|
Probe - Hot Wire
|
|
Meas. Range
|
0 to +20 m/s
|
|
Resolution
|
0.01 m/s
|
|
Probe - Vane
|
|
Meas. Range
|
0 to +60 m/s
|
|
Resolution
|
0.01m/s (60 vane)
0.1 m/s (16 vane)
|
For calibration on this instrument please call us on 01420 544 433